GMS-1700

GMS-1700

GMS-1700

Introduction
GMS-1700 is a multi-point gas alarm that is connected to a plurality of gas detectors to monitor gas leakage in a complex way. Each detector installed in the field is connected 1:1 with the receiver in the integrated panel and transmits the concentration signal to the central monitoring unit at the same time.
The GMS-1700 outputs and transmits a RELAY OUTTPUT, 4-20mA standard current signal to implement comprehensive gas monitoring. Through this, it is possible to build an integrated monitoring environment with external devices such as PLC/DDC, various RECODERS, and COMPUTER.
Features
- Multiple detectors and receivers are concentrated in one place in a 1:1 connection method, respectively, and it is a multi-point receiver that performs the integrated monitoring function.
- Simultaneously receive 4-20mA analog continuous signals from multiple detectors and use high-resolution A/D converters Accurately represent digital signals.
- By programming various functions with the microprocessor, the user's arbitrary monitoring environment can be built. (Ex. AL1, AL2 Alarm Range, AL1, AL2 Alarm Delay Time setting, etc.)
- High-resolution D/A converter outputs 4-20mA standard current signal and transmits accurate signal to external controller (PLC/DDC).
- AIn case of AL1, AL2 alarm, AL1, AL2 Relay Output function is provided for interworking with FAN and externalalarm device.
- It is a product with a built-in lithium-ion battery.
Specification
Specification
Installation Method wall-mounted
Control Structure Alarm UNIT: 1, Receive Unit: 4
Detector Connection type For multi-point type (4 connected detectors)/4 circuit
Input Power AC100~240VAC/60§Ô
Battery Power DC24V 2.5AH
Input Signal 4-20§Ì DC/F.S
Output Signal 4-20§Ì DC/F.S
Out Voltage 24 V (5 A)
Alarm Signal Low Alarm - AL1 (RED)
High Alarm - AL2 (RED)
Failure alarm - FAULT LED (YELLOW)
Alarm Method Time - LED blinking
Hearing - Buzz Bass (over 80§¼)
Alarm Value Setting AL1, AL2 2-stage alarm-user arbitrarily set
Alarm Delay Time 0~99 sec user arbitrarily set
Clear Alarm Manual and automatic return
Alarm Output 2-stage (AL1, AL2) alarm RELAY CONTACT
Operating Temperature -10¡É ~50¡É
Operating Humidity 5~95%RH (Non-Condensing)
Display 3 color 1.8 inch 3 - Digit 7 Segmeut.
Normal(Green), AL1(Orange), AL2(Red)
¡Ø Blinking